Sprinkler Contractor's Material & Test Certificate (NFPA 13)

A Contractor's Material & Test Certificate for Aboveground Piping documents the installation, hydrostatic testing, and acceptance of a new fire sprinkler system per NFPA 13, following the form structure used by AHJs nationwide (e.g. Philadelphia's TP_005_F and Delaware's identical form). It records equipment approval, owner instruction, sprinkler specification, welding QC, and the hydrostatic test result.

NFPA 13 (Standard for the Installation of Sprinkler Systems), state/local fire codes and AHJ acceptance-test requirementsValid: One-off (acceptance test, no expiry)

No credit card required. Set up in 30 seconds.

Sample Sprinkler Material & Test Cert certificate

Sample Sprinkler Contractor's Material & Test Certificate (NFPA 13) certificate created with CertBox, showing the professional PDF layout with installation conformance to accepted plans, sprinkler make, model, orifice size and temperature rating, welding qc (aws b2.1/asme ix) where applicable

Sample Sprinkler Material & Test Cert with fictional data. All personal details shown are fake.

What it covers

  • Installation conformance to accepted plans
  • Sprinkler make, model, orifice size and temperature rating
  • Welding QC (AWS B2.1/ASME IX) where applicable
  • Hydrostatic test at 200 PSI for 2 hours (or 50 PSI above static above 150 PSI)
  • Owner instruction and O&M/NFPA 25 documentation left on premises
  • Caps/straps removed and control valves left open at handover

Who needs a Sprinkler Material & Test Cert?

Fire sprinkler contractors
General contractors
AHJ/fire marshal inspectors
Building owners (new construction)

Create your Sprinkler Material & Test Cert with CertBox

1

Fill in the form

Pick Sprinkler Material & Test Cert from the list, fill in the fields on your phone.

2

Compliance checks run

Built-in validation catches missing fields and out-of-range readings.

3

PDF generated instantly

Professional PDF ready to share via secure link or download.

Frequently asked questions about Sprinkler Material & Test Cert

What hydrostatic test pressure does NFPA 13 require?
New aboveground sprinkler piping must be hydrostatically tested at 200 PSI for 2 hours, or at 50 PSI in excess of the maximum static pressure where that static pressure exceeds 150 PSI — with no leakage.
Why does the form ask about welding certification?
Where sprinkler piping is welded, NFPA 13 requires welders to be qualified under AWS B2.1 or ASME Section IX, and requires cutouts/discs to be retrieved as part of quality control — both are standard attestations on the real Contractor's Material & Test Certificate.