This certificate documents the NFPA 20 acceptance test of a new or modified fire pump — churn (no-flow), 100% and 150% rated-flow performance, driver startup, and controller/alarm verification — before the pump is placed in service.

NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection)Valid: One-off (no expiry)

No credit card required. Set up in 30 seconds.

Sample Fire Pump Acceptance certificate

Sample Fire Pump Acceptance Test Certificate certificate created with CertBox, showing the professional PDF layout with pump nameplate data and driver type, churn (no-flow) pressure against the 140% limit, 100% and 150% rated-flow test results

Sample Fire Pump Acceptance with fictional data. All personal details shown are fake.

What it covers

  • Pump nameplate data and driver type
  • Churn (no-flow) pressure against the 140% limit
  • 100% and 150% rated-flow test results
  • Suction pressure and driver startup verification
  • Controller alarms, transfer switch and overspeed trip tests

Who needs a Fire Pump Acceptance?

Fire protection contractors
General contractors
Building owners
AHJs witnessing acceptance

Create your Fire Pump Acceptance with CertBox

1

Fill in the form

Pick Fire Pump Acceptance from the list, fill in the fields on your phone.

2

Compliance checks run

Built-in validation catches missing fields and out-of-range readings.

3

PDF generated instantly

Professional PDF ready to share via secure link or download.

Frequently asked questions about Fire Pump Acceptance

What is the churn pressure limit for a fire pump?
NFPA 20 requires the no-flow (churn) pressure not exceed 140% of the pump’s rated pressure. A higher reading indicates a problem that should be investigated before acceptance.
What must a fire pump deliver at 150% of rated flow?
At 150% of rated flow, a centrifugal fire pump must maintain at least 65% of its rated pressure. Where the water supply cannot sustain 150% flow, the test is run at the maximum available flow and recorded as supply-limited.