Fire Pump Inspection & Test

This report documents routine NFPA 25 fire pump testing — the weekly or monthly no-flow (churn) run, or the annual flow test at 0%/100%/150% of rated capacity — with driver, controller and battery condition checks recorded alongside the readings.

NFPA 25 Chapter 8 (Inspection, Testing and Maintenance of Water-Based Fire Protection Systems — Fire Pumps)Valid: Weekly or monthly (no-flow test); annual (flow test) per NFPA 25

No credit card required. Set up in 30 seconds.

Sample Fire Pump ITM certificate

Sample Fire Pump Inspection & Test certificate created with CertBox, showing the professional PDF layout with no-flow (churn) test readings and mechanical checks, annual flow test at 0%/100%/150% of rated capacity, driver, controller and standby battery condition

Sample Fire Pump ITM with fictional data. All personal details shown are fake.

What it covers

  • No-flow (churn) test readings and mechanical checks
  • Annual flow test at 0%/100%/150% of rated capacity
  • Driver, controller and standby battery condition
  • Deficiencies and next test due date

Who needs a Fire Pump ITM?

Fire protection contractors
Facility managers
Property managers with in-house or contracted pump testing

Create your Fire Pump ITM with CertBox

1

Fill in the form

Pick Fire Pump ITM from the list, fill in the fields on your phone.

2

Compliance checks run

Built-in validation catches missing fields and out-of-range readings.

3

PDF generated instantly

Professional PDF ready to share via secure link or download.

Frequently asked questions about Fire Pump ITM

How often must a fire pump be churn tested?
Diesel-driven pumps are churn tested weekly (minimum 30-minute run). Electric-driven pumps are also weekly by default, though NFPA 25 permits monthly testing where a recognized remote monitoring system is in place.
What does the annual flow test check?
The annual test runs the pump at churn, 100% and 150% of rated capacity to confirm it still meets its original performance curve — churn pressure within 140% of rated, and at least 65% of rated pressure at 150% flow.