R-290 — GWP, safety class & UK F-Gas status

Propane · natural. Future-proof · ultra-low GWP under UK F-Gas rules — full readout, replacements and timeline below.

R-290

Propane · natural

Safety A3HC
3GWP (AR4)
0750 split ban2,500 service ban4,000
Future-proof · ultra-low GWP
UK F-Gas
No F-Gas quota impact. Highly flammable (A3), so charge is strictly limited by room size and it is mainly used in sealed monobloc heat pumps and small packs.
Typical use
Monobloc heat pumps, small commercial
ODP
0

UK F-Gas phase-down timeline

Where the wider phase-down stands.

  1. 2015

    R-22 servicing ban

    No virgin or reclaimed HCFCs for servicing. The original ozone phase-out completes.

  2. 2020

    High-GWP service ban

    Virgin F-Gas with GWP of 2,500 or more banned for refrigeration of 40 tCO₂e or more — hits R-404A / R-507A.

  3. Jan 2025

    New single-split ban

    New single-split AC systems containing under 3 kg of F-gas cannot use refrigerants of 750 GWP or more (retained EU 517/2014, Annex III) — rules out R-410A and R-407C.

  4. 2030

    Quota squeeze

    The HFC quota drops to about 21% of the 2015 baseline and the reclaimed/recycled exemption for GWP 2,500+ servicing ends — R-404A / R-507A become effectively unavailable.

  5. 2032

    Monobloc ban (EU)

    EU Regulation 2024/573 bans F-gases in new self-contained / monobloc AC and heat pumps up to 12 kW. GB retains EU 517/2014 and has not adopted this step — DEFRA consulted on GB reform (closed Dec 2025), response due 2026.

  6. 2035

    Split ban (EU)

    EU Regulation 2024/573 bans F-gases in new split AC and heat pumps up to 12 kW. Not yet GB law — GB still follows retained EU 517/2014 pending the delayed HFC phase-down reform.

Frequently asked questions about R-290

Is R-290 banned in the UK?

No F-Gas quota impact. Highly flammable (A3), so charge is strictly limited by room size and it is mainly used in sealed monobloc heat pumps and small packs.

What is R-290's GWP (Global Warming Potential)?

R-290 has a GWP of 3 on an AR4 basis — below both UK F-Gas thresholds (750 and 2,500 GWP).

What replaces R-290?

R-290 is current-generation in this reference — there's no listed replacement for it.

Is R-290 flammable?

R-290 is ASHRAE 34 safety class A3. It is flammable, so it needs appropriately rated tools, leak detection and charge-limit checks.