R-449A — GWP, safety class & UK F-Gas status

HFO/HFC blend. R-404A / R-22 retrofit under UK F-Gas rules — full readout, replacements and timeline below.

R-449A

HFO/HFC blend

Safety A1HFC/HFO blend
1,397GWP (AR4)
0 750 split ban 2,500 service ban4,000
R-404A / R-22 retrofit
UK F-Gas
A popular mid-GWP blend for retrofitting R-404A and R-22 systems. Above 750 and quota-affected.
Typical use
Commercial refrigeration retrofit
ODP
0

GWP = Global Warming Potential (100-year, CO₂ = 1) · ODP = Ozone Depletion Potential · safety class per ASHRAE Standard 34.

UK F-Gas phase-down timeline

Where the wider phase-down stands.

  1. 2015

    R-22 servicing ban

    No virgin or reclaimed HCFCs for servicing. The original ozone phase-out completes.

  2. 2020

    High-GWP service ban

    Virgin F-Gas with GWP of 2,500 or more banned for refrigeration of 40 tCO₂e or more — hits R-404A / R-507A.

  3. Jan 2025

    New single-split ban

    New single-split AC systems containing under 3 kg of F-gas cannot use refrigerants of 750 GWP or more (retained EU 517/2014, Annex III) — rules out R-410A and R-407C.

  4. Jan 2027

    GB quota step (unchanged by the reform)

    The existing GB HFC quota drops a further 22.6%. DEFRA consulted on a more ambitious phase-down (closed Dec 2025) but confirmed in May 2026 it will not legislate in 2026, so this step applies as written — expect price and availability pressure on higher-GWP gases rather than a change of rules.

  5. 2030

    Quota squeeze

    The HFC quota drops to about 21% of the 2015 baseline and the reclaimed/recycled exemption for GWP 2,500+ servicing ends — R-404A / R-507A become effectively unavailable.

  6. 2032

    Monobloc ban (EU)

    EU Regulation 2024/573 bans F-gases in new self-contained / monobloc AC and heat pumps up to 12 kW (the same rule already caps them at 150 GWP from 2027). GB retains EU 517/2014 and has NOT adopted this step: DEFRA consulted on GB reform (closed Dec 2025) and confirmed in May 2026 that it will not legislate in 2026, with a response summarising feedback due later in the year.

  7. 2035

    Split ban (EU)

    EU Regulation 2024/573 bans F-gases in new split AC and heat pumps up to 12 kW. Larger splits above 12 kW are capped at 750 GWP from 2029 and 150 from 2033 under the same regulation. None of this is GB law — GB still follows retained EU 517/2014, and the GB reform was deferred in May 2026.

Frequently asked questions about R-449A

Is R-449A banned in the UK?

A popular mid-GWP blend for retrofitting R-404A and R-22 systems. Above 750 and quota-affected.

What is R-449A's GWP (Global Warming Potential)?

R-449A has a GWP of 1,397 on an AR4 basis — above the 750 GWP new-split limit but below the 2,500 GWP service-ban threshold.

What replaces R-449A?

R-449A is current-generation in this reference — there's no listed replacement for it.

Is R-449A flammable?

R-449A is ASHRAE 34 safety class A1. It is classed non-flammable (A1/B1).